FP-001-02 Smoke Detector Sensitivity Verification
From the Australian Standards (AS1851) FP-001-02 sub-committee room, smoke detector sensitivity verification is proposed to be the replacement for the current 'go/no-go' test of smoke detectors. These changes are proposed to replace the current requirement in AS1851:2005 in table 6.4.2 Item 2.31.
The proposed changes consider the requirements of various detector types including; collective, collective auto-recalibrating with CIE indication, collective auto-recalibrating without CIE indication and analogue addressable.
Sensitivity testing also provides for a significant reduction in the current testing frequency from 50% go/no-go per annum to 20% sensitivity verification per annum.
Note: The verification shall be carried out such that over a five year period the sensitivity of all detectors have been verified.
It is proposed that these amendments be published in July 2007.